ACTUATOR FUNCTION | TRIP-RESET |
ARC QUENCHING METHOD | AIR |
BODY LENGTH | 64.6 MILLIMETERS NOMINAL |
BODY STYLE | SINGLE POLE TYPE |
BODY WIDTH | 30.0 MILLIMETERS NOMINAL |
CASE MATERIAL | PLASTIC |
CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATION OR OVERVOLTAGE SINGLE LOCATION |
MANUAL ACTUATOR TYPE AND QUANTITY | 1 PUSH-PULL |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 7.5 AMPERES AC SINGLE LOCATION AND 7.5 AMPERES DC SINGLE LOCATION |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1000.0 AC SINGLE LOCATION |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | GENERAL PURPOSE |
POLE QUANTITY | 1 |
MOUNTING FACILITY TYPE AND QUANTITY | 1 THREADED BUSHING |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 115.0 AC SINGLE LOCATION AND 208.0 AC SINGLE LOCATION AND 28.5 DC SINGLE LOCATION |
RESET METHOD | MANUAL |
TERMINAL TYPE AND QUANTITY | 2 SCREW |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 1000.00 NOMINAL AT 150 PCT SINGLE LOCATION AND 48.00 NOMINAL AT 200 PCT SINGLE LOCATION AND 6.00 NOMINAL AT 300 PCT SINGLE LOCATION AND 1.50 NOMINAL AT 400 PCT SINGLE LOCATION AND 0.45 NOMINAL AT 1000 PCT SINGLE LOCATION AND 0.10 NOMINAL AT 2000 PCT SINGLE LOCATION |
TRIP RELEASE AMBIENT TEMP RATING | 20.0 DEG CELSIUS NOMINAL SINGLE LOCATION |
TRIP RELEASE CHARACTERISTIC | TIME DELAY SINGLE LOCATION |
TRIP RELEASE METHOD | THERMAL SINGLE LOCATION |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 135.0 SINGLE LOCATION |
ULTIMATE TRIP TIME PER POLE IN SECONDS | 0.1 MINIMUM SINGLE LOCATION AND 1000.0 MAXIMUM SINGLE LOCATION |